Terminals: "F2"" Quick disconnect tabs (.0250"X 0.032")Case: High-impact polystyreneCharging Cycle Applications: Limit initial current to 2000mA. Charge until battery voltage (undercharge) reaches 14.40 to 14.70 volts at 68' F (20' C). Hold at 14.40 to 14.70 volts until current drops to approximately 100mA. Battery is fully charged under these conditions, and charger should either be disconnected or switched to "float" voltage. "Float" or "Stand-by Service": Hold battery across constant voltage source of 13.50 to 13.80 volts continuously. When held at this voltage, the battery will seek its own current level and maintain itself in a fully charged condition. : PS-12100-F2-4CTN |
|
|
|